National Electrical Code, NEC, Article 430.32 – Motor Overload Protection
The National Electrical Code, NEC Article 430.32 focuses on the overload protection of motors. Overloads occur when a motor draws excessive current, leading to overheating and potential failure. To prevent damage, the NEC electrical codes mandate overload protection based on the motor’s full-load current (FLC) and service factor.
Table of Contents
Table of Contents

This article explains the requirements of Article 430 of the National Electrical Code, ensuring compliance with motor overload protection rules. It also covers the importance of sizing overloads for motors, the relationship between overload relay for motor protection, and how to use the Cable Size for Motor Calculator to determine the correct wiring.
Understanding the National Electrical Code, NEC, Article 430.32
What is Article 430 of the National Electrical Code?
Article 430 NEC provides installation and protection guidelines for motors, controllers, and branch circuits. Section 430.32 of the NEC code USA specifically deals with motor overload protection, ensuring that motors are safeguarded against prolonged overcurrent conditions.
The National Electrical Code 430 states that motors must be protected using overload devices, which prevent excessive heating due to sustained overloading. These devices include thermal overload relays and electronic overload relays, designed to disconnect the motor before critical damage occurs.
Overload Protection According to National Electrical Code, NEC, Article 430.32
The NEC electrical codes specify overload protection based on motor type and service factor. The overload settings must be selected carefully to avoid nuisance trips while providing sufficient protection.
Motor Overload Protection Calculator
Overload Setting for Motor Protection (NEC 430.32 Guidelines)
Motor Type | Service Factor (SF) | Maximum Overload Setting |
---|---|---|
Motors with SF 1.15 or greater | 125% of FLC | 115% – 125% of rated current |
Motors with SF less than 1.15 | 115% of FLC | 100% – 115% of rated current |
Motors with nameplate temperature rise not exceeding 40°C | 115% of FLC | 100% – 115% of rated current |
These values ensure that motors operate within safe temperature limits. Overload relay for motor applications use these settings to prevent overheating.
Importance of Motor Service Factor in Overload Protection
The motor service factor (SF) is a multiplier that indicates how much a motor can handle above its rated power. For example, a 1.15 SF motor can operate at 15% above its rated capacity under normal conditions.
NEC 430.32 overload settings depend on service factor because motors with a higher SF can handle more overload before tripping.
Calculating Overload Protection for Motors Using NEC 430.32
To determine the correct overload setting for motor protection:
- Find the full-load current (FLC) from the motor nameplate.
- Identify the motor service factor (e.g., 1.15, 1.0).
- Apply the NEC 430.32 overload percentage based on service factor.
Example Calculation for Overload Protection
Consider a 3-phase, 10 HP motor, 460V, with a service factor of 1.15:
- Full-load current (FLC) from NEC Table 430.248 = 14A
- Overload setting (125% of FLC, per NEC 430.32) = 14 × 1.25 = 17.5A
Thus, the overload relay for motor protection should be set at 17.5A.
Selecting the Right Overload Relay for Motor Protection
Overload relays are crucial in motor protection as per National Electrical Code 430. The most common types include:
- Thermal Overload Relays: Use bimetallic strips to detect heat and trip at set limits.
- Electronic Overload Relays: More precise, with adjustable settings based on motor FLC.
Proper selection of an overload relay for motor ensures compliance with NEC electrical codes and prevents damage due to sustained overloading.
Cable Sizing for Motor Circuits Under NEC Article 430
Determining Cable Size for Motor Circuits
The correct cable size for motor circuits depends on factors like motor FLC, service factor, and voltage drop. Using a Cable Size for Motor Calculator helps ensure compliance with NEC code USA.
Cable Size for Motor Chart (Based on NEC)
Motor HP | Voltage (V) | FLC (A) | Recommended Cable Size |
---|---|---|---|
5 HP | 230V | 28A | 10 AWG |
10 HP | 460V | 14A | 12 AWG |
20 HP | 460V | 27A | 8 AWG |
50 HP | 460V | 65A | 4 AWG |
International Standards: IEC Standard for Instrument Earthing
The IEC standard for instrument earthing differs slightly from NEC electrical codes. While the NEC emphasizes overload protection, the IEC focuses on grounding safety.
Selecting the correct earthing cable size as per IEC ensures electrical safety and compliance with international regulations.
Conclusion: Ensuring Compliance with National Electrical Code, NEC, Article 430.32
Understanding and applying National Electrical Code, NEC, Article 430.32 is essential for safe motor operation. Proper overload relay for motor protection, overload setting for motor, and correct cable size for motor ensure compliance with NEC code USA.
Follow Us on Social:
Subscribe our Newsletter on Electrical Insights to get the latest updates in Electrical Engineering.
MotorOverloadProtection, #NEC430, #ElectricalSafety, #OverloadRelay, #MotorProtection, #ElectricalEngineering, #NECCompliance, #IndustrialMotors, #MotorOverload, #ElectricalCode, #NECRegulations, #ThermalOverloadRelay, #MotorSafety, #ElectricMotors, #CodeCompliance