IEC Standard for Air Circuit Breaker
Understanding the IEC Standard for Air Circuit Breaker
Air Circuit Breakers (ACBs) are critical components in medium and low-voltage power distribution systems. They provide protection against overcurrents, short circuits, and other electrical faults. To ensure their performance, safety, and reliability, ACBs must meet certain international guidelines. The IEC standard for air circuit breaker governs their design, testing, and operation.

This standard is primarily defined in IEC 60947-2, which outlines the general requirements for circuit breakers, including air circuit breakers. For engineers, technicians, and facility operators, understanding this IEC framework ensures proper selection, installation, and maintenance of ACBs in compliance with global safety norms.
What Is an Air Circuit Breaker (ACB)?
An air circuit breaker is a type of electrical protection device that interrupts fault currents using air as the arc extinguishing medium. These breakers are usually deployed in power control centers, switchboards, and large industrial plants. Unlike oil or vacuum circuit breakers, ACBs are easier to maintain and are ideal for applications where environmental conditions are controlled.
Key features include:
- High breaking capacity
- Adjustable protection settings
- On-site maintenance capability
- Real-time monitoring with digital trip units
These features make air circuit breakers suitable for LV and MV systems up to 690V and sometimes beyond, depending on the design.
Know more about IEC Standard for Cable Lugs
Overview of the IEC Standard for Air Circuit Breaker
The IEC 60947-2 standard provides detailed specifications for low-voltage circuit breakers. It ensures product consistency across manufacturers, enhancing safety, compatibility, and efficiency. This standard specifies requirements for:
- Performance under normal and abnormal conditions
- Mechanical and electrical endurance
- Tripping characteristics
- Temperature rise limits
- Short-circuit making and breaking capacity
Table 1: Key Parameters Specified in IEC 60947-2
Parameter | Description |
---|---|
Rated Insulation Voltage (Ui) | Maximum voltage ACB can withstand without breakdown |
Rated Impulse Withstand Voltage | Resistance against transient overvoltages |
Rated Service Short-Circuit Capacity (Ics) | The highest fault current ACB can interrupt repeatedly |
Rated Ultimate Short-Circuit Capacity (Icu) | The maximum fault level breaker can interrupt once |
Mechanical Endurance | Number of mechanical operations without failure |
Electrical Endurance | Number of operations under load before failure |
The standard aims to unify testing and classification, making ACBs globally compatible and safe for integration into any electrical distribution system.
Know more about IEC Standard for Cable Tray
Types of ACBs and Their IEC Classifications
IEC 60947-2 classifies circuit breakers into Type B, Type C, and Type D based on their tripping characteristics. While this classification is more commonly associated with MCBs, the principle of time-current curve classification applies to ACBs as well, particularly with programmable trip settings.
For ACBs, trip units are either thermal-magnetic or electronic. The IEC standard for air circuit breaker defines the current-time characteristics and the selectivity levels that must be adhered to.
Electronic trip units offer:
- Long-time delay
- Short-time delay
- Instantaneous trip
- Ground fault protection
These trip characteristics must fall within the ranges defined in the IEC standard to be compliant.
Testing Requirements in IEC 60947-2
The IEC standard for air circuit breaker outlines rigorous testing conditions to ensure safety and reliability. These tests include:
- Dielectric Testing: Ensures insulation withstands high voltages
- Temperature Rise Test: Checks heating under rated current
- Short-circuit Testing: Verifies ability to interrupt fault currents
- Mechanical Operation Test: Assesses endurance over many cycles
- Tripping Test: Confirms tripping at set values and timing
ACBs are tested for coordination with other protective devices, which is crucial for system selectivity and reliability.
Table 2: Example Test Sequence for ACB under IEC 60947-2
Test Type | Objective | Conditions |
---|---|---|
Thermal Test | Check temperature limits | Rated current for extended period |
Dielectric Strength | Verify insulation | Applied voltage 2.5kV – 5kV depending on Ui |
Breaking Capacity | Confirm interruption without damage | Icu and Ics tests at specified fault level |
Endurance Test | Assess durability | 10,000 mechanical, 2,000 electrical cycles |
Compliance with these test conditions is mandatory for certification.
Know more about Contact Resistance Test IEC Standard
Ratings Defined by IEC
The IEC standard for air circuit breaker sets multiple rating definitions:
- Rated Operational Voltage (Ue): Voltage during normal operation
- Rated Current (In): Max current the ACB can carry continuously
- Rated Frequency: Typically 50Hz or 60Hz
- Rated Short-Time Withstand Current (Icw): The max short-circuit current ACB can carry for a specified time (1s or 3s) without tripping
Understanding these ratings is essential when designing panels or choosing ACBs for large electrical systems.
Coordination and Selectivity
Another critical area addressed by the IEC standard for air circuit breaker is selectivity and coordination. Selectivity ensures only the faulty section of a power system is isolated, preserving system integrity.
IEC 60947-2 defines:
- Zone Selective Interlocking (ZSI): A feature in advanced ACBs allowing faster fault isolation
- Backup Protection Requirements: Ensures that upstream breakers can clear faults if downstream fails
- Time-Current Curves Matching: Guarantees that protection devices do not overlap inappropriately
These features help in avoiding unnecessary shutdowns and improve operational efficiency.
Marking and Documentation
As per IEC 60947-2, all ACBs must have clear markings and documentation including:
- Manufacturer’s name and product type
- Rated operational and insulation voltage
- Short-circuit capacities
- Tripping curve or trip class
- Date code and serial number
Manufacturers are also required to provide a compliance certificate and detailed instruction manual for installation and maintenance in line with IEC guidelines.
Know more about Circuit Breaker Timing Test Procedure
Importance of IEC Compliance
Using an ACB that meets the IEC standard for air circuit breaker has the following benefits:
- Enhanced Safety: Reduced fire and arc risks
- Operational Reliability: Breakers perform consistently under defined loads
- Global Compatibility: Supports cross-border installations
- Audit Readiness: Meets insurance and inspection standards
- Long-Term Efficiency: Reduces failure, unplanned downtime, and repair costs
IEC compliance isn’t just a technical requirement—it’s a legal and operational necessity in many industrial environments.
Real-World Application Example
Consider a 4000A-rated ACB installed in a data center’s main LV panel. The designer must ensure:
- The Icu value is higher than the maximum fault level at the point of installation
- Selective coordination with downstream MCCBs or MCBs
- Compliance with dielectric withstand and temperature rise requirements
- Trip unit is programmable for real-time monitoring
- Proper markings for maintenance teams
Only ACBs complying with IEC 60947-2 can provide the performance and safety required for such critical applications.
Future of IEC Standards in ACBs
With the advent of smart grids and digital protection systems, the IEC standard for air circuit breaker is evolving. New revisions of the IEC 60947 series incorporate:
- Communication protocols like Modbus and Ethernet
- Integration with SCADA and BMS
- Predictive maintenance via sensor feedback
- Cybersecurity features for remote access
Manufacturers are now offering intelligent ACBs that comply not only with mechanical standards but also digital data communication requirements as per latest IEC guidelines.
Know more about Primary Injection Test vs Secondary Injection Test
Conclusion
The IEC standard for air circuit breaker, primarily defined under IEC 60947-2, is vital for ensuring that ACBs meet international safety and performance benchmarks. From design to deployment, every aspect of an ACB is governed by this standard, offering guidance on electrical ratings, mechanical strength, fault current interruption, and more.
Follow Us on Social:
Subscribe our Newsletter on Electrical Insights to get the latest updates in Electrical Engineering.
#IECAirCircuitBreaker, #AirCircuitBreakerStandards, #IECElectricalStandards, #CircuitBreakerSafety, #ElectricalProtection, #IndustrialCircuitBreakers, #IEC60947, #ACBStandards, #ElectricalEngineering, #SwitchgearProtection, #IECCompliance, #PowerDistributionSafety, #LowVoltageSwitchgear, #ElectricalCodes, #CircuitBreakerTesting