Benshaw Soft Starter Problems Explained: Common Faults, Causes & Proven Fixes
Benshaw soft starters are widely used in industrial motor control systems to reduce inrush current, limit mechanical stress, and extend equipment life. Despite their solid reputation, users often face operational issues during installation, commissioning, or long-term operation. Understanding benshaw soft starter problems in detail helps maintenance teams minimize downtime, avoid unnecessary replacements, and keep motors running efficiently.

Table of Contents
This guide explains the most common faults, their root causes, and proven fixes based on real-world industrial practices. Whether you are an electrical engineer, technician, or plant supervisor, this article will help you diagnose issues faster and more accurately.
Know more about Difference Between Star Delta and DOL Starter: A Comprehensive Guide
Understanding How a Benshaw Soft Starter Works
Before troubleshooting, it is important to understand the basic operation. A Benshaw soft starter controls motor voltage using SCRs to gradually ramp up current during startup. This controlled acceleration reduces electrical stress and mechanical shock on motors and driven loads.
When problems occur, they usually relate to:
- Incorrect electrical parameters
- Improper installation or wiring
- Environmental conditions
- Motor or load-related issues
Many benshaw soft starter problems can be resolved without replacing the unit if the fault is correctly identified.
Common Benshaw Soft Starter Problems and Their Symptoms
The table below summarizes frequently reported issues along with typical symptoms seen in industrial settings.
| Problem Area | Common Symptoms | Likely Impact |
|---|---|---|
| Overcurrent faults | Starter trips during acceleration | Motor fails to reach full speed |
| Phase loss or imbalance | Fault alarm after startup | Motor overheating |
| SCR failure | Motor hums or does not start | Production downtime |
| Bypass contactor issues | Excessive heat in starter | Reduced efficiency |
| Control power faults | Display not powering on | Complete system shutdown |
Each of these benshaw soft starter problems has specific causes that must be addressed systematically.
Overcurrent Trips During Motor Start
One of the most common benshaw soft starter problems is overcurrent tripping during startup.
Causes
- Incorrect motor full load current setting
- Load inertia higher than expected
- Ramp time set too short
- Mechanical binding in the driven equipment
When the motor draws current above the programmed limit, the starter protects itself by tripping.
Know more about How does the star delta starter reduce starting current? Important Concepts
Proven Fixes
- Verify motor nameplate current and re-enter correct values
- Increase acceleration ramp time gradually
- Inspect the mechanical load for jamming or misalignment
- Check motor bearings and coupling condition
Proper current configuration alone resolves many benshaw soft starter problems related to nuisance tripping.
Phase Loss and Voltage Imbalance Faults
Phase-related faults are serious and should never be ignored. Benshaw soft starters continuously monitor incoming power quality.
Causes
- Loose power terminals
- Blown upstream fuse
- Uneven supply voltage
- Faulty power cable
These benshaw soft starter problems often appear intermittently, making them harder to diagnose.
Proven Fixes
- Tighten all line and load terminals to manufacturer torque values
- Measure line-to-line voltage with a calibrated meter
- Replace damaged cables or fuses
- Ensure supply voltage remains within acceptable tolerance
Ignoring phase imbalance can lead to motor overheating and insulation failure.
Know more about Motor Starter Types: A Powerful Guide with 7 Key Options You’ll Appreciate
SCR and Power Module Failures
SCR failure is one of the more costly benshaw soft starter problems, but it usually develops over time rather than suddenly.
Common Indicators
- Motor does not accelerate smoothly
- Starter trips immediately after start command
- Visible overheating or burn marks
Root Causes
- Repeated high-current starts
- Poor ventilation inside the panel
- Excessive ambient temperature
- Improper heat sinking
Proven Fixes
- Improve panel ventilation and airflow
- Limit starts per hour according to specifications
- Verify cooling fans are operational
- Replace damaged SCR modules if necessary
Preventive maintenance significantly reduces SCR-related benshaw soft starter problems.
Know more about Motor Starter Size Chart: 7 Essential Insights for Better Selection
Bypass Contactor Not Engaging
Most Benshaw soft starters use a bypass contactor to reduce heat after startup. Failure of this component leads to inefficiency and overheating.
| Symptom | Possible Cause | Corrective Action |
|---|---|---|
| Starter runs hot | Bypass contactor stuck open | Inspect coil and contacts |
| High energy loss | Incorrect bypass wiring | Recheck control wiring |
| Audible noise | Contactor chattering | Verify control voltage stability |
Bypass issues are often overlooked, yet they contribute to long-term benshaw soft starter problems if left unresolved.
Control Power and Display Issues
A blank display or unresponsive keypad can stop operations completely.
Causes
- Control fuse failure
- Incorrect control voltage selection
- Loose control wiring
- Internal power supply fault
Proven Fixes
- Check control voltage rating and jumper settings
- Replace blown control fuses
- Verify grounding continuity
- Inspect control transformer output
Many benshaw soft starter problems reported as “dead units” are resolved through basic control power checks.
Parameter Setting and Programming Errors
Incorrect settings are responsible for a large percentage of benshaw soft starter problems, especially after new installations or maintenance.
Common Mistakes
- Wrong motor horsepower selection
- Excessively low current limit
- Incorrect start or stop profile
- Disabled protective functions
Recommended Actions
- Always program using motor nameplate data
- Use factory default settings as a baseline
- Adjust parameters step-by-step, not all at once
- Document changes for future reference
Accurate programming improves reliability and simplifies troubleshooting.
Know more about VFD vs Soft Starter: Key Differences You Must Know for Motor Control
Environmental Factors Affecting Performance
Environmental conditions play a major role in the long-term reliability of soft starters.
| Environmental Issue | Effect on Starter | Preventive Measure |
|---|---|---|
| High temperature | SCR overheating | Add panel cooling |
| Dust accumulation | Short circuits | Regular cleaning |
| Moisture | Corrosion | Use sealed enclosures |
| Vibration | Loose connections | Secure mounting |
Many recurring benshaw soft starter problems disappear once environmental conditions are controlled.
Preventive Maintenance Tips to Avoid Future Problems
Preventive maintenance is the most effective way to minimize benshaw soft starter problems.
- Inspect power and control terminals quarterly
- Clean cooling fans and air vents
- Review fault history logs periodically
- Verify parameter settings after outages
- Test bypass contactor operation
These simple actions reduce unexpected failures and extend equipment life.
When to Repair vs Replace a Benshaw Soft Starter
Not all benshaw soft starter problems justify replacement.
Repair is recommended when:
- Faults are related to wiring or settings
- SCR modules are replaceable
- Control power issues are external
Learn more about servo motor interview questions
Replacement is justified when:
- Multiple SCR failures occur
- Control boards are obsolete
- Repair cost exceeds unit value
A proper assessment avoids unnecessary capital expenditure.
Final Thoughts
Understanding benshaw soft starter problems requires a structured troubleshooting approach rather than guesswork. Most issues stem from configuration errors, power quality problems, or environmental factors rather than internal defects. By identifying symptoms early and applying proven fixes, engineers can significantly reduce downtime and improve motor system reliability.
With correct installation, accurate parameter settings, and routine maintenance, Benshaw soft starters remain a dependable solution for industrial motor control applications.