IEC Standard for Relay Coordination – Complete Guide to Protection and Coordination Studies
Relay coordination is one of the most critical aspects of electrical power system protection. The IEC standard for relay coordination provides clear guidelines and methodologies to ensure that protective relays work in harmony to isolate only the faulty section of the system while keeping the rest of the network operational.

Table of Contents
In large industrial and utility networks, uncoordinated relays can cause unnecessary outages, equipment damage, and safety risks. Understanding the IEC framework helps engineers design selective, reliable, and efficient protection systems.
Understanding the Concept of Relay Coordination
Relay coordination refers to setting protective devices so that the relay closest to the fault operates first, while upstream relays act as backups. The goal is selective tripping—only the faulted section should disconnect.
In a power network with multiple protective devices, this coordination prevents unnecessary interruptions. The IEC standard for relay coordination defines time-current curves, selectivity criteria, and grading margins that engineers must follow for different types of relays.
The IEC standards, especially IEC 60255 and IEC 60947, define the general requirements for protection relays and low-voltage circuit breakers. These standards ensure accuracy, dependability, and interoperability among devices from different manufacturers.
Importance of IEC Standard for Relay Coordination
Using the IEC standard for relay coordination is crucial for safety and reliability. When relays are coordinated according to IEC guidelines, the system ensures proper sequence of operation during faults. The importance lies in:
- Minimizing power outages and equipment damage
- Preventing cascading trips in interconnected systems
- Ensuring operator and equipment safety
- Achieving compliance with international protection standards
- Reducing downtime and improving overall system stability
In industrial networks, improper coordination may lead to complete plant shutdowns. Hence, following IEC coordination principles is both a technical and economic necessity.
Know more about IEC Standard for Vibration Testing – IEC 60068 Explained with Procedures and Requirements
IEC Standards Governing Relay Coordination
Several IEC standards directly or indirectly influence relay coordination practices. The following table summarizes the most relevant ones:
| IEC Standard | Description | Application |
|---|---|---|
| IEC 60255 | Measurement and control relays | Defines performance, testing, and functional requirements |
| IEC 60947-2 | Circuit breakers | Specifies trip coordination between circuit breakers and overload relays |
| IEC 60909 | Short-circuit current calculations | Provides fault current values needed for coordination studies |
| IEC 61850 | Communication for substations | Standardizes digital communication and coordination logic |
| IEC 61439 | Low-voltage switchgear assemblies | Defines selectivity and coordination for LV protection systems |
These standards work together to ensure that protection relays, breakers, and communication systems coordinate efficiently.
Key Principles in IEC Standard for Relay Coordination
Time Grading
The IEC standard for relay coordination recommends time grading between relays based on fault current magnitude and operating characteristics. For overcurrent protection, a minimum time margin of 0.3 to 0.5 seconds is often maintained between primary and backup relays. This ensures that backup relays only trip if the primary fails.
Current Grading
In radial systems, the current grading method ensures that relays with lower pickup currents operate before those with higher settings. This is effective when fault current varies significantly along the feeder length.
Energy Selectivity
In low-voltage systems, circuit breakers use energy-based selectivity (I²t selectivity) defined in IEC 60947-2. This ensures that downstream breakers trip faster for short circuits, while upstream devices remain intact.
Zone Protection
The IEC standard also supports zone-based coordination, where the protection system is divided into zones like generator, transformer, busbar, and feeder. Each zone has defined protection boundaries and coordination overlap.
Know more about IEC Standard for Vacuum Circuit Breaker – IEC 62271 Guidelines, Ratings & Testing Explained
Discrimination Types
According to IEC, discrimination (or selectivity) between devices can be:
- Time discrimination: Based on time delay difference
- Current discrimination: Based on pickup setting difference
- Energy discrimination: Based on let-through energy
- Logic discrimination: Based on communication-assisted schemes
IEC 60255 and Relay Coordination
IEC 60255 is the backbone of the IEC standard for relay coordination. It defines testing procedures, performance limits, and response times for relays under normal and fault conditions.
It also ensures interoperability, so that relays from different manufacturers respond predictably when coordinated in a network.
IEC 60255 addresses several critical aspects like:
- Time-current characteristic curves (TCCs)
- Accuracy of operating time
- Tolerances in pickup and dropout
- Temperature and vibration endurance
- Functional safety and dependability
Through these parameters, the standard helps engineers accurately model relay behavior in coordination studies.
Coordination between Overcurrent and Earth Fault Relays
Overcurrent and earth fault protection are the most common areas where IEC coordination is applied. Both relays must be set carefully to ensure that the faulted feeder clears without affecting the rest of the system.
| Parameter | Overcurrent Relay | Earth Fault Relay |
|---|---|---|
| Pickup current | 120–150% of max load | 20–40% of rated current |
| Time delay margin | 0.3–0.5 s | 0.2–0.4 s |
| Coordination type | Time-current | Time-current |
| Standard reference | IEC 60255 | IEC 60255-151 |
Proper setting ensures that the earth fault relay operates only during ground faults, while the overcurrent relay responds to phase faults.
Know more about IEC Standard for Voltage Drop Calculation: Best Guide
IEC Standard for Relay Coordination in Industrial and Utility Systems
In industrial power systems, motor protection, transformer feeders, and distribution panels rely on precise relay coordination. The IEC standard provides detailed methods for setting inverse time curves such as Standard Inverse (SI), Very Inverse (VI), and Extremely Inverse (EI).
Utilities often adopt the IEC inverse curves to ensure that relays coordinate for a wide range of fault currents. For example, in a radial distribution network, the downstream feeder relay uses a very inverse curve, while upstream substations use a standard inverse setting. This creates smooth time discrimination and ensures selectivity.
Example of Coordination Grading
| Relay Location | Curve Type | Pickup Current (A) | Time Multiplier | Grading Margin (s) |
|---|---|---|---|---|
| Feeder Relay (R1) | Very Inverse | 150 | 0.2 | – |
| Substation Relay (R2) | Standard Inverse | 300 | 0.4 | 0.4 |
| Grid Relay (R3) | Standard Inverse | 600 | 0.6 | 0.4 |
This example shows how relays at different levels are set with progressive time delays to achieve proper coordination.
Role of IEC 60909 in Relay Coordination
IEC 60909 defines the method for calculating short-circuit currents in power systems. These calculations are the foundation of relay coordination studies. Engineers use them to determine fault levels, select relay pickup settings, and check if protection devices can safely interrupt fault currents.
Without accurate short-circuit data, even properly coordinated relays may fail to operate correctly. IEC 60909 ensures that fault levels are consistent, realistic, and standardized for global use.
Know more about IEC Standard for VRLA Battery – Complete Guide to Design, Testing, and Performance
Digital Coordination under IEC 61850
Modern substations are increasingly digital, using IEC 61850 for communication between Intelligent Electronic Devices (IEDs). The standard allows logic-based coordination using signals like GOOSE (Generic Object-Oriented Substation Events).
With IEC 61850, relays can share real-time fault information, enabling faster tripping, self-healing, and adaptive protection. This approach minimizes mechanical delays and ensures that coordination is both selective and dynamic.
For instance, during a bus fault, the breaker failure relay can instantly signal other IEDs via IEC 61850 to isolate the affected zone within milliseconds.
Common Challenges in Implementing IEC Relay Coordination
Despite clear standards, practical coordination can be challenging. Some common issues include:
- Incorrect fault current estimation
- Overlapping protection zones
- Relay setting errors or communication delays
- Equipment aging and calibration drift
- Mixed-brand relay integration
To overcome these challenges, engineers use software tools like ETAP, DigSILENT PowerFactory, and CYME that support IEC-based coordination studies. These tools simulate faults, plot time-current curves, and validate grading margins automatically.
Best Practices for IEC Standard-Based Coordination
Following best practices ensures reliable implementation of the IEC standard for relay coordination:
- Perform detailed short-circuit studies before setting relays
- Maintain a minimum grading margin of 0.3–0.5 seconds
- Test and calibrate relays periodically as per IEC 60255
- Verify selectivity after system modifications
- Use communication-assisted schemes in complex networks
- Document all relay settings and curve types
These practices guarantee that coordination remains effective even as load patterns and equipment change over time.
Know more about Best Rotor Earth Fault Protection for Brushless Generator | Working, Types & Settings Explained
Benefits of Following IEC Standard for Relay Coordination
Applying IEC coordination standards brings several measurable advantages:
- Enhanced reliability and uptime of power systems
- Reduced risk of equipment failure and safety hazards
- Standardized settings and testing procedures
- Easier system expansion and equipment replacement
- Compliance with international engineering codes
Organizations adopting these standards also find it easier to integrate new digital relays, maintain consistent settings, and pass regulatory audits.
Conclusion
The IEC standard for relay coordination provides a universal framework for designing safe, selective, and efficient protection systems. From IEC 60255 defining relay behavior to IEC 60909 guiding fault current calculations and IEC 61850 enabling digital coordination, these standards together create a robust protection ecosystem.
When implemented properly, IEC-compliant coordination minimizes fault impact, improves network reliability, and ensures compliance with international norms. For modern power systems—whether industrial or utility—the adoption of IEC-based coordination is no longer optional. It is a cornerstone of electrical protection engineering that ensures safety, stability, and performance in every power network.