Generator Sizing Calculator for VFD Motors

|

Generator sizing for VFD motors is a technical process that ensures efficient motor performance and system stability. When pairing a generator with variable frequency drive (VFD) motors, understanding load characteristics, harmonics, and transient behavior becomes critical. Getting the size right means protecting the generator, the motor, and the connected equipment.

Unlike standard motors, VFD motors are powered through electronic drives. These drives convert AC power into DC and then back to variable-frequency AC. This conversion process causes additional stress on the generator if it’s not sized correctly.

Importance of Generator Sizing for VFD Motors

Correct generator sizing for VFD motors ensures voltage stability, minimizes harmonic distortion, and avoids nuisance tripping. A mismatch can lead to overheating, waveform distortion, or even generator failure. When undersized, the generator struggles during load changes. If oversized, it becomes inefficient and costly.

Generators feeding VFDs need to deal with both non-linear loads and inrush current. Non-linear loads cause waveform distortion. The generator must have low reactance and sufficient capacity to absorb these disturbances.

How VFDs Affect Generator Sizing

VFDs impact generator performance in three major ways—harmonics, voltage dips, and power factor. Harmonics from VFDs distort the waveform. Voltage dips occur when motors start or ramp up under load. Power factor changes based on motor load and frequency.

Generators should be designed with enough margin to handle these effects. Typically, a generator should be sized at least 1.5 to 2 times the VFD motor’s full load kVA. But this value depends on many factors.

Generator Sizing for VFD Motors: Basic Formula

There is no universal formula, but engineers often use this approach:

Generator kVA = Motor kW × Load Factor × VFD Factor × Safety Margin

  • Motor kW is the rated power of the motor.
  • Load Factor is typically between 1.1 to 1.25.
  • VFD Factor compensates for harmonic distortion and power factor (usually 1.3 to 1.5).
  • Safety Margin covers future expansion or startup surges (generally 1.1 to 1.25).

Let’s take a 75 kW motor:

Generator kVA = 75 × 1.2 × 1.4 × 1.15 ≈ 145 kVA

Recommended Generator Oversizing Guidelines

Motor Size (kW)Minimum Generator Size (kVA)Oversize Factor
11 kW25 – 30 kVA2.3 – 2.7
30 kW60 – 70 kVA2.0 – 2.3
75 kW140 – 160 kVA1.8 – 2.1
110 kW200 – 230 kVA1.8 – 2.1
200 kW360 – 420 kVA1.8 – 2.1

These values vary based on harmonic filtering, load type, and application criticality.

Factors That Influence Generator Sizing for VFD Motors

Several technical parameters affect generator sizing for VFD motors. Here’s a breakdown:

Harmonic Distortion:
VFDs generate harmonics that distort generator voltage. This causes heating in the windings and leads to lower power quality. THD (Total Harmonic Distortion) should be kept below 5%. Using harmonic filters or reactors helps mitigate this issue.

Voltage Regulation:
During motor startup or torque surge, voltage drops. The generator’s AVR (Automatic Voltage Regulator) must respond quickly. AVR performance becomes crucial when using VFDs, which are sensitive to voltage fluctuations.

Motor Inertia and Load Type:
High-inertia loads like conveyors and fans demand more energy during acceleration. This causes torque spikes. The generator must handle short-term overload without instability.

Power Factor Variation:
VFDs typically have a poor power factor at low speeds. Generators must have enough capacity to maintain stable voltage at these conditions. Sometimes, power factor correction devices are needed.

Cable Lengths and EMI:
Long cable runs from generator to VFDs may induce electromagnetic interference (EMI). Shielded cables and grounding methods become necessary. While it doesn’t directly impact sizing, it influences performance.

Line Reactors and Filters:
Installing line reactors can smooth out current draw and reduce harmonics. Passive filters help the generator maintain a cleaner waveform. With these, the oversize factor can be slightly reduced.

Practical Example of Generator Sizing for VFD Motors

Imagine a plant operating a 132 kW pump motor with a VFD. The load is non-linear and includes torque surges.

Step 1:
Motor rating = 132 kW
Step 2:
Load Factor = 1.2
VFD Factor = 1.4
Safety Margin = 1.15

Generator Size = 132 × 1.2 × 1.4 × 1.15 = 255.6 kVA

You round up to 260 or 275 kVA to include any auxiliary loads.

If harmonics are well controlled with filters, the factor could be reduced. For unfiltered systems, staying at or above 2.0 times motor kW is safe.

Generator Impedance and VFD Sensitivity

VFDs are voltage-sensitive. Any transient from the generator may cause it to trip. This makes generator impedance an important specification. Low impedance generators offer better voltage recovery. Choose a generator with a sub-transient reactance (X”d) below 15% when supplying VFDs.

THD Limits in Generator Sizing for VFD Motors

IEEE Standard 519 recommends maintaining THD at:

  • Less than 5% for voltage distortion
  • Less than 8% for current distortion at PCC (Point of Common Coupling)

Generators must be selected and rated considering these thresholds. If distortion exceeds limits, apply filters or increase generator size.

Generator Sizing for Multiple VFD Motors

When multiple VFD motors run on a single generator, the challenge grows. Total load must be calculated with diversity and simultaneity in mind. Peak load scenarios must be simulated to ensure stability.

Let’s say you have:

  • One 45 kW motor
  • One 30 kW motor
  • Two 15 kW motors

Total = 45 + 30 + (2 × 15) = 105 kW
With a 1.4 VFD factor and 1.2 load factor:

Generator size = 105 × 1.4 × 1.2 = 176.4 kVA
You choose a 200 kVA generator for safety.

Role of Inverter Duty Generators

Standard generators may not work well with VFD loads. Inverter-duty generators are designed to tolerate the harmonic-rich environment of VFD systems. They have higher thermal capacities and are better equipped to maintain waveform integrity.

For applications like HVAC systems, mining, or industrial drives using VFDs, inverter-duty generators are a preferred option.

Why Undersizing Is Risky

Undersized generators can lead to:

  • Frequent tripping of VFDs
  • Overheating of the generator windings
  • Failure to maintain voltage during startup
  • Degraded motor performance
  • Increased maintenance and downtime

Generator Sizing Software and Manufacturer Guidelines

Most generator manufacturers offer tools for accurate sizing. These take into account voltage dips, recovery time, harmonic levels, and load profiles. Examples include:

  • Cummins Power Suite
  • CAT Electric Power SpecSizer
  • KOHLER Power Solutions Sizing Tool

Using manufacturer guidelines adds reliability to the sizing process.

Conclusion on Generator Sizing for VFD Motors

Proper generator sizing for VFD motors is more than matching power ratings. It requires understanding harmonics, dynamic loading, voltage recovery, and drive characteristics. Oversizing alone doesn’t solve the problem—it must be engineered for stability, reliability, and clean power.

Use filters, choose low impedance generators, and apply conservative factors. In critical operations, always test the setup under real conditions before commissioning.

Generator sizing for VFD motors is the foundation of reliable and efficient motor-driven systems. Getting it right pays off in uptime, energy savings, and peace of mind.

Subscribe our Newsletter on Electrical Insights to get the latest updates in Electrical Engineering.


#GeneratorSizing, #VFDmotors, #MotorControl, #ElectricalEngineering, #PowerSystemDesign, #IndustrialAutomation, #GeneratorCalculator, #VFDApplications, #LoadCalculation, #BackupPower, #SizingTool, #SmartPower, #EngineeringTools, #GeneratorLoad, #ElectricalDesign