Related Posts to Read

4 Comments

  1. Hello, the cable size reference is incorrect. The NEC has stipulations for 4/0 and larger, stipulations for cables less that 4/0 and also rules for having both in a single cable tray.

    1. According to NEC 392.22(A)(1), cable fill limits differ based on conductor size.

      For single-conductor cables 4/0 AWG and larger, refer to Table 392.22(A).

      For cables smaller than 4/0 AWG, the fill area must not exceed 50% of the tray cross-sectional area.

      When both types are installed together, the most restrictive fill area must be used.

      1. I agree with your response. I whole heartedly agree that the NEC has rules to dictate the fill based on if the cable is larger than 4/0 or smaller than 4/0.

        I don’t think I explained the issue correctly. This page, that I am currently on has a couple of errors. You use the cable size No. 4 AWG instead of using No. 4/0 AWG.

        At the top of the page it states the following:
        -Cables with No. 4 AWG or Larger Conductors (THIS SHOULD SAY “CABLES WITH No. 4/0 AWG or Larger Conductors)
        -Cables with conductors No. 4 AWG or larger (THIS SHOULD SAY 4/0 LARGER) cannot be stacked on top of each other.
        -Cables with Smaller Than No. 4 AWG Conductors (THIS SHOULD SAY “CABLES WITH No. 4/0 AWG or Smaller Conductors)
        -On the other hand, cables with smaller than No. 4 AWG (THIS SHOULD SAY 4/0) conductors are allowed to be stacked on top of each other.

        Thank you!

Leave a Reply

Your email address will not be published. Required fields are marked *