Capacitor Bank Sizing for Power Factor Correction – Step by Step
Improving power factor is one of the most cost-effective ways to enhance the efficiency of electrical systems in industrial and commercial facilities. Poor power factor not only causes higher utility bills but also reduces the available capacity of the distribution system. Capacitor banks are widely used for power factor correction because they supply reactive power locally and reduce the reactive burden on the grid. The challenge many engineers and plant managers face is accurate capacitor bank sizing. Without the right calculation method, the correction may be insufficient or even lead to over-compensation.
Table of Contents
Table of Contents

This guide explains capacitor bank sizing in a step-by-step process with technical depth and practical examples. If you prefer automation, you can use my Power Factor Correction Calculator to simplify the process. However, understanding the underlying method is essential before relying on any tool.
Key takeaways:
- Capacitor bank sizing is based on the required reactive power (kVAR) to shift power factor to the desired value.
- The formula depends on active power (kW), present power factor, and target power factor.
- Proper sizing improves energy efficiency, lowers demand charges, and optimizes transformer and cable capacity.
Why Capacitor Bank Sizing is Important
In any AC electrical system, load consumes two types of power: active power (kW) and reactive power (kVAR). Active power does the real work, like running motors and lighting, while reactive power maintains magnetic fields in inductive devices. A low power factor indicates that too much reactive power is being drawn, which increases current and system losses.
Know more about Power Factor Correction Devices to Buy for Home in our detailed article.
Utilities often impose penalties on consumers with low power factor. Correctly sizing a capacitor bank reduces this reactive power demand. By adding capacitors, the phase difference between current and voltage decreases, resulting in a higher power factor. The outcome is lower losses, reduced transformer loading, and cost savings. Capacitor bank sizing is, therefore, both a technical and financial necessity.
Basics of Power Factor and Capacitor Bank Sizing
Power factor is defined as the ratio of active power (kW) to apparent power (kVA). Mathematically:
Power Factor = kW ÷ kVA
The apparent power combines active and reactive components:
kVA = √(kW² + kVAR²)
Capacitors supply leading reactive power, which cancels out the lagging reactive power from inductive loads. The required capacitor size is the amount of kVAR that needs to be added to improve the power factor from the initial value (cosθ1) to the desired value (cosθ2).
The general formula is:
Required kVAR = kW × (tanθ1 – tanθ2)
Where:
- θ1 = angle of initial power factor
- θ2 = angle of target power factor
This formula is the foundation of capacitor bank sizing and is used in both manual and automated calculations.
Know more about Automatic Power Factor Correction Using Arduino in our detailed article.
Step by Step Capacitor Bank Sizing
Now, let’s walk through capacitor bank sizing step by step.
Step 1: Identify Load Parameters
The first step is to collect load data. You need the following values:
- Active power (kW) or demand load
- Present power factor (cosθ1)
- Target power factor (cosθ2)
These values can be obtained from utility bills, load meters, or power analyzers installed in the system.
Step 2: Calculate Current Reactive Power
From the present power factor, calculate the reactive power being consumed.
Reactive Power (Q1) = kW × tanθ1
For example, if the system load is 500 kW with a power factor of 0.75:
θ1 = cos⁻¹(0.75) = 41.41°
Q1 = 500 × tan(41.41°) = 500 × 0.9004 = 450 kVAR
Use our online tool Power Factor Correction Capacitor Calculator
Step 3: Determine Desired Reactive Power
For the target power factor, calculate the new reactive power.
Reactive Power (Q2) = kW × tanθ2
Suppose the desired power factor is 0.95:
θ2 = cos⁻¹(0.95) = 18.19°
Q2 = 500 × tan(18.19°) = 500 × 0.328 = 164 kVAR
Step 4: Calculate Required Capacitor kVAR
Now, subtract the two values to find the required capacitor size.
Required kVAR = Q1 – Q2 = 450 – 164 = 286 kVAR
Therefore, for a 500 kW load, you need a capacitor bank of around 286 kVAR to improve power factor from 0.75 to 0.95.
Step 5: Select Capacitor Bank Units
Capacitor banks are available in standard ratings, such as 25 kVAR, 50 kVAR, 100 kVAR, etc. Choose a combination close to the calculated requirement. For example, you can select:
- Two units of 100 kVAR
- One unit of 50 kVAR
- One unit of 25 kVAR
- One unit of 10 kVAR
This provides flexibility for step control in automatic power factor correction (APFC) panels.
Capacitor Bank Sizing Example Table
Here is a simplified example of capacitor bank sizing for different power factors for a 500 kW load:
Initial PF | Target PF | Required kVAR |
---|---|---|
0.70 | 0.95 | 331 kVAR |
0.75 | 0.95 | 286 kVAR |
0.80 | 0.95 | 239 kVAR |
0.85 | 0.95 | 189 kVAR |
0.90 | 0.95 | 120 kVAR |
This table shows how the capacitor requirement decreases as the initial power factor gets closer to the desired value.
Know more about Power Factor Correction Devices
Factors Affecting Capacitor Bank Sizing
While the formula gives the basic capacitor requirement, practical considerations can affect the final choice:
- Load Variation: Industrial loads fluctuate throughout the day. Automatic power factor correction panels with step-controlled capacitors are preferred over fixed banks.
- Harmonics: Systems with high harmonic distortion require detuned reactors with capacitor banks to prevent resonance.
- System Voltage: Capacitors are rated for specific voltages. Ensure the capacitor voltage matches or exceeds system voltage.
- Over-compensation: Adding too much capacitance can lead to a leading power factor, which also causes issues. Always size carefully.
Benefits of Correct Capacitor Bank Sizing
Accurate capacitor bank sizing leads to multiple technical and financial benefits:
- Reduced utility penalties due to improved power factor.
- Increased capacity of transformers and cables.
- Lower system losses and reduced voltage drops.
- Better equipment performance due to stable voltage levels.
- Extended lifespan of electrical infrastructure.
These benefits highlight why capacitor bank sizing is more than just a compliance requirement. It’s an investment in long-term efficiency.
Practical Tips for Capacitor Bank Sizing
- Always verify the utility’s target power factor requirement, as penalties vary by region.
- Avoid installing a single large capacitor bank in fluctuating load environments. Instead, use automatic step control.
- Regularly monitor the system using power analyzers to ensure the correction remains effective.
- If harmonic levels are above IEEE 519 limits, consider detuned capacitor banks.
Know more about Power Factor Correction Methods
Capacitor Bank Sizing in Large Installations
For large plants, capacitor bank sizing is often done at multiple levels:
- Individual Motor Capacitors: Installed directly at motor terminals.
- Group Capacitors: Connected at distribution boards.
- Central Bank: Installed at main incomer with automatic controllers.
This layered approach ensures localized correction and minimizes current flow across feeders.
Using Software and Calculators for Capacitor Bank Sizing
While manual calculation is useful for understanding, real-world systems are complex. Load variations, harmonic effects, and transformer ratings make manual calculations time-consuming. That’s why software tools and online calculators are helpful.
My Power Factor Correction Calculator allows you to input load, initial PF, and target PF to instantly find the required kVAR. It is accurate, quick, and reduces the chances of errors. However, engineers should still understand the manual method explained above to validate results.
Conclusion
Capacitor bank sizing is a critical part of power factor correction. It requires careful calculation of reactive power, based on the existing and desired power factors. By applying the step-by-step method explained in this guide, engineers and facility managers can optimize system performance, reduce utility costs, and extend equipment life.
For practical use, you can simplify the process with my Power Factor Correction Calculator, which instantly provides capacitor bank sizing values. Still, having a solid understanding of the manual calculation ensures you make informed decisions and avoid over- or under-compensation.