What is the Protection Scheme of an Alternator Against Inter Turn Fault?

|

Alternators are at the heart of power generation in most industrial and utility applications. They convert mechanical energy into electrical energy and are critical to maintaining reliable supply. However, these machines are not immune to faults. One of the most dangerous and least easily detected faults is the inter turn fault in an alternator. It may seem minor initially but can escalate rapidly, leading to severe damage and prolonged downtime. This article explores what inter turn faults are, why they occur, and the protection schemes used to detect and prevent them in alternators.

What is the Protection Scheme of an Alternator Against Inter Turn Fault?
What is the Protection Scheme of an Alternator Against Inter Turn Fault?

Understanding Inter Turn Fault in an Alternator

An inter turn fault in an alternator is a type of internal winding fault. It occurs when insulation between two or more turns of the same winding fails. This causes the current to bypass a section of the winding, creating a short circuit loop within the same phase.

This loop leads to localized heating, excessive circulating currents, and potential damage to the winding. Because the fault does not cause an immediate change in terminal voltage or external current, traditional differential protection schemes may fail to detect it.

Let’s break this down with a technical perspective.

Why Inter Turn Fault is Critical

When an inter turn fault happens:

  • A small voltage drives a large circulating current between the affected turns.
  • This creates a localized hot spot.
  • Over time, thermal stress damages insulation further.
  • The fault spreads and can escalate to a phase-to-phase or phase-to-ground fault.
  • Such major faults can destroy the stator core and windings.

Since alternators are expensive and vital, detecting these early signs is crucial.

know more about What are the Different Types of Faults in a Power System?

Causes of Inter Turn Faults in Alternators

There are several technical reasons behind an inter turn fault in an alternator. Understanding these helps us build better protection schemes:

  • Aging of insulation material due to heat, vibration, and contamination
  • Mechanical vibration of the rotor or stator
  • Switching surges and overvoltages
  • Loose windings or coil movement
  • Poor manufacturing practices

These faults typically start small and go undetected unless proper protective relays are in place.

Protection Scheme Against Inter Turn Fault in an Alternator

Detecting inter turn faults requires specific protection strategies. Here are the main schemes used:

1. Split Phase Differential Protection

This is one of the most effective schemes to protect against inter turn faults in large alternators.

In this method, the winding of each phase is split into two equal halves. The current flowing through each half is measured using separate current transformers (CTs). Under healthy conditions, the currents are balanced. If an inter turn fault occurs, the circulating current causes an imbalance, which the relay detects.

ParameterValue for Detection
Current imbalance thresholdTypically 10–15% deviation
Detection sensitivityHigh (detects early stage)
SuitabilityLarge turbo alternators

This scheme requires special winding arrangements, which may not be available in all alternators.

know more about Types of Alternator Protection

2. Negative Sequence Current Protection

Inter turn faults lead to unbalanced three-phase currents. This unbalance introduces negative sequence components in the stator currents. Protection relays monitor these components.

If negative sequence current exceeds a set threshold (typically around 10% of rated current) for a preset time, the relay operates.

However, this protection may not detect faults that are very close in the winding or during light load conditions.

3. Axial Flux Detection (for Turbo Alternators)

An inter turn fault in an alternator generates additional axial flux in the stator core. This flux can be detected using axial flux detectors or search coils placed at the ends of the stator.

These coils produce a voltage signal proportional to the axial flux. Sudden increases indicate a possible inter turn fault.

This method is expensive but very effective in large machines, especially hydrogen-cooled turbo alternators.

know more about Differential Protection of Alternator

4. Thermal Protection

Thermal protection relays indirectly detect inter turn faults by monitoring winding temperature.

Since inter turn faults generate heat, temperature sensors embedded in stator windings detect abnormal rise. If the temperature crosses a preset threshold, a trip signal is issued.

Although thermal relays offer good long-term protection, they are not fast-acting and may not detect small inter turn faults early.

5. Partial Discharge Monitoring

Partial discharge (PD) is a high-frequency event that occurs due to insulation degradation. Online PD monitoring systems can detect early signs of insulation failure.

If PD activity rises above a safe level, maintenance teams can schedule repairs before a full fault occurs.

PD monitoring is non-intrusive and very useful for condition-based maintenance.

Comparative Overview of Inter Turn Fault Protection Schemes

Protection SchemeDetection SpeedCostSensitivityApplicability
Split Phase DifferentialFastHighVery HighLarge Alternators
Negative Sequence RelayModerateLowModerateAll Alternators
Axial Flux DetectionFastVery HighHighTurbo Alternators
Thermal ProtectionSlowMediumLowGeneral Applications
PD MonitoringEarly WarningHighHighCritical Machines

know more about CT Polarity for Differential Protection

Practical Challenges in Inter Turn Fault Protection

Despite having advanced protection schemes, some challenges remain in real-world implementation:

  • Cost of instrumentation in older or small generators
  • False trips due to harmonics or transient conditions
  • Limited installation space for search coils or split CTs
  • Need for coordinated settings in multi-relay systems
  • Relay sensitivity calibration across different load profiles

Therefore, protection engineers must design schemes based on machine size, criticality, and budget.

Best Practices to Minimize Inter Turn Faults in Alternators

Along with protection, prevention is key. Here are some best practices:

  • Use high-quality insulation materials with proper class ratings
  • Ensure tight winding construction and vibration damping
  • Avoid frequent overloading or voltage fluctuations
  • Perform regular insulation resistance tests
  • Install temperature and flux monitoring sensors

Routine maintenance and condition monitoring reduce fault probability and extend alternator life.

know more about Overcurrent Protection of Transformer

Conclusion: Why Inter Turn Fault Protection is Vital

An inter turn fault in an alternator may seem minor in the early stage, but its impact can be catastrophic. It is one of the few faults that traditional protection schemes may overlook unless dedicated protection methods are installed.

Modern alternator protection schemes like split-phase differential, axial flux monitoring, negative sequence relays, and PD monitoring help detect and isolate faults early. Protection relays must be selected carefully based on machine type, rating, and criticality.

Subscribe our Newsletter on Electrical Insights to get the latest updates in Electrical Engineering.


#InterTurnFault, #AlternatorProtection, #GeneratorFaults, #ElectricalProtection, #PowerSystemProtection, #RelayProtection, #InterTurnFaultInAlternator, #FaultDetection, #GeneratorSafety, #ElectricalEngineering, #AlternatorFaults, #ProtectionRelays, #TransformerAndAlternator, #EngineeringExplained, #PowerGeneration