Fault Current Division Factor: Best Guide
The fault current division factor is a key concept in electrical power systems. It describes how fault current splits among different parallel paths during a fault. Understanding this factor helps engineers protect equipment, ensure safety, and maintain power system reliability.
In any fault scenario, whether it is a short circuit or line-to-ground fault, current flows through multiple paths. These paths could include generators, transformers, or transmission lines. The division of this current is not equal. It depends on the impedance of each path. This is where the fault current division factor comes in. It gives us a numerical way to understand and predict how current flows through each path.

In power systems, calculating the exact share of fault current going into different branches is essential. This allows engineers to design protective devices such as circuit breakers and fuses properly. Without understanding this concept, there is a risk of undersized protection, leading to equipment failure.
Importance of Fault Current Division Factor
The fault current division factor is important for several reasons. It plays a role in relay coordination, system stability, and the sizing of protection equipment. When multiple sources or paths are available, the fault current doesn’t go entirely through one route. Instead, it divides based on impedance values.
For instance, in fault current distribution in star delta transformer, the star winding and delta winding may share the fault current unequally. Their impedance and connection style cause this behavior. The division factor tells us how much current goes through each winding. Knowing this helps protect transformers from thermal damage or mechanical stress.
This factor is also helpful when transformers are connected in parallel. If the impedance is not matched, one transformer may carry more fault current than the other. That can damage insulation or windings. So, accurate calculations are necessary.
How Fault Current Division Factor Works
The fault current division factor is calculated based on the impedance of the various paths available during a fault. It relies on Ohm’s law and network analysis techniques. In simple terms, lower impedance paths carry more current, while higher impedance paths carry less.
The basic formula is:
Fault Current Division Factor for Path A = Total Equivalent Impedance / Impedance of Path A
Iₐ = I_total × (Z_total / Zₐ)
Where:
- Iₐ is the current through Path A
- I_total is the total fault current
- Z_total is the equivalent impedance of all parallel paths
- Zₐ is the impedance of Path A
This formula allows us to find the share of current each path takes based on its impedance.
Practical Example of Fault Current Division Factor
Imagine a fault occurs at a bus connected to two parallel transformers. Transformer T1 has an impedance of 0.1 ohm, and Transformer T2 has 0.2 ohm. The total fault current is 3000 A.
Impedance Table
Transformer | Impedance (Ohm) | Inverse Impedance (1/Z) |
---|---|---|
T1 | 0.1 | 10 |
T2 | 0.2 | 5 |
Total | – | 15 |
The proportion of current through T1 is:
T1 Share = 10 / (10 + 5) = 2 / 3 = 66.7%
Current through T1 = 0.667 × 3000 = 2000 A
Current through T2 = 0.333 × 3000 = 1000 A
This example shows how the fault current division factor helps split the fault current. The transformer with lower impedance (T1) carries more current.
Fault Current Division Factor in Different Systems
In a radial system, fault current often comes from a single direction. In this case, division factor is less critical. But in ring or meshed systems, multiple paths are available. Fault current division becomes a central issue. The fault current of transformer in such a setup must be carefully studied to avoid overloads.
In systems with both grid and generator supply, the division factor can change with switching conditions. For instance, if a local generator is connected, its impedance path becomes available. The fault current may divide between the grid and the generator.
Application in Fault Current Calculation
The fault current calculation process involves several steps. It includes determining the location of the fault, calculating total fault current, and applying the division factor. This helps find the current flowing in each equipment branch.
Steps to Use Fault Current Division Factor
- Identify all paths contributing to the fault.
- Calculate impedance of each path.
- Compute inverse impedance (1/Z) for each path.
- Sum all inverse impedances to get the total.
- Determine the current division ratio for each path.
- Multiply the total current by the ratio for each path.
This process ensures every component is properly rated. It avoids overloading and damage during a fault.
Fault Current Division in Star Delta Transformer
The fault current distribution in star delta transformer depends on the winding configuration. A star winding offers a neutral point for grounding. A delta winding lacks that. In a line-to-ground fault, most current flows through the star winding. Delta may carry little to no ground fault current.
However, for line-to-line or three-phase faults, both windings can carry significant currents. The division factor will be based on the impedance of each side and the type of fault.
In three-phase transformers with unequal winding impedance, division factor also changes. Engineers must carefully compute it during the fault current calculation stage.
Impedance Considerations
Impedance is not just resistance. It also includes reactance. For transformers and cables, reactance can be significant. Fault current division factor must consider both resistance and reactance:
Z = √(R² + X²)
Also, transformer impedance is given as a percentage. You must convert this to actual ohms based on transformer rating before using it in the division factor formula.
Sample Impedance Conversion
If a 5 MVA transformer has 5% impedance at 11 kV:
Z_base = (11 × 11) / 5 = 121 / 5 = 24.2 ohms
Z_actual = 0.05 × 24.2 = 1.21 ohms
Use this value in the fault current division factor formula.
Factors Affecting Fault Current Division Factor
Many factors affect the fault current division factor:
- Transformer Impedance
- Cable Length and Size
- Generator Internal Impedance
- Fault Location
- Type of Fault (LG, LL, LLG, LLLG)
For example, in a distant fault, cable impedance may dominate. In that case, current through that path reduces. Closer paths carry more current.
In star-delta transformers, the zero-sequence impedance affects the division in ground faults. This adds complexity to calculations.
Importance in Protection Coordination
Protection engineers rely on accurate division factor calculations. Relays and breakers must trip only for faults they are meant to detect. If a path carries less current than expected, a breaker may not trip. That leaves the fault unattended, risking damage.
Accurate fault current division factor helps design correct relay settings. This ensures selectivity and fast isolation of the fault.
Software Tools for Division Factor
Several simulation tools help with this:
- ETAP
- DIgSILENT PowerFactory
- PSCAD
These allow detailed modeling of all elements. They also provide graphical output for fault current paths. However, engineers must still understand the theory to validate the results.
Conclusion
The fault current division factor is a critical concept in power system engineering. It helps determine how current splits among different paths during a fault. This understanding is vital for designing reliable and safe electrical networks.
From transformer protection to cable sizing, and from breaker rating to relay coordination, this factor touches every part of the system. The concept becomes even more crucial in complex configurations, such as those involving multiple power sources or transformers.
Follow Us on Social:
Subscribe our Newsletter on Electrical Insights to get the latest updates in Electrical Engineering.
#FaultCurrent, #CurrentDivision, #PowerSystemProtection, #ElectricalEngineering, #ShortCircuitAnalysis, #FaultAnalysis, #PowerSystemDesign, #EngineeringCalculations, #CurrentFlow, #ProtectionSystem, #ElectricalFaults, #CircuitAnalysis, #GridProtection, #PowerFaults, #ElectricalSafety